Facts checked on 19 November 2026. Published by MDG Services on 22 November 2026.
Density is how heavy a litre of fuel is. It is measured at a standard 15 degrees C, because fuel swells when warm. This page follows the public sector oil companies' guideline (MDG 2024); a private company's pump should ask for its own. As on 19 November 2026.
When does the dealer check density?
| When | What | Source |
|---|---|---|
| Tanker arrives | Match the recorded density at 15 degrees C on the invoice with the actual product | MDG 2024, 1.1 |
| Before unloading | Draw a sample from each compartment after draining about 20 litres; check density and temperature, record it | MDG 2024, 1.2(viii) |
| After unloading | Dispense at least 50 litres, then sample at the nozzle and record the density at 15 degrees C in the density register | MDG 2024, 1.2(xiv) |
| Every morning | Draw a nozzle sample and record the opening density at 15 degrees C before sales | MDG 2024, 1.4.1(c) |
What does the tanker check allow?
The dealer converts the reading with the ASTM tables (53B) and checks it is within +/- 3.0 kg per cubic metre of the invoice density MDG 2024, 1.2(iv). The Control Order, as amended on 15 March 2024, gives the limit as +/- 0.0030, with no unit named in its text, and asks for a record of densities MS and HSD Amendment Order 2024. In case of doubt about quality, ask the supply location or the area field officer MDG 2024, 1.2(ix).
Which range does BIS give?
BIS shows these ranges at 15 degrees C for BS VI fuel, from 2020: petrol (IS 2796) 720-775 kg per cubic metre, diesel (IS 1460) 810-845 BIS petroleum standards deck.
What must the pump keep?
- Calibrated hydrometers and thermometers, and the ASTM conversion table, in working order and available to inspectors MDG 2024, 1.5(vi).
- The daily sales register and the density register for the current and previous financial years MDG 2024, 5.1.12.
What happens without a morning reading?
An inspector treats it as no reference density. Sales and supplies of all products are suspended, samples go to a lab, and penal action follows, in line with adulteration if the sample fails MDG 2024, 5.1.9. See records and marketing discipline, tanks and quality complaints. Our density guide for MDG 2024 goes deeper.
Where this comes from
- Marketing Discipline Guidelines 2024, Bharat Petroleum: clauses 1.1, 1.2, 1.4, 1.5, 5.1.
- MS and HSD Amendment Order 2024, MoPNG: density variation and records.
- BIS note on petroleum standards: density ranges.
Questions people ask
01What is density in a petrol pump?
In practice, it is the weight of fuel for a given volume, read at 15 degrees C so that readings taken at different temperatures can be compared. The oil company's invoice states it, and the dealer records it MDG 2024, 1.1 and 1.2.
02How is density checked at a petrol pump?
The dealer draws a sample from the tanker or nozzle in a clear container and reads density and temperature, then converts it to 15 degrees C with the ASTM tables MDG 2024, 1.2. Calibrated hydrometers, thermometers and the ASTM table must be kept MDG 2024, 1.5.
03What should the density of petrol be?
The BIS table for BS VI petrol (IS 2796) shows 720 to 775 kg per cubic metre at 15 degrees C BIS petroleum standards deck. In a lab test, the reference is the invoice density up to unloading, then the tank reading after 50 litres are dispensed MDG 2024, chapter 2.
04How much can tanker density differ from the invoice?
Not more than +/- 3.0 kg per cubic metre in the guideline MDG 2024, 1.2(iv); the Control Order gives +/- 0.0030, with no unit named MS and HSD Amendment Order 2024.
05By what time must the morning density be recorded?
By 10 AM every day MDG 2024, 5.1.9. Without it, an inspector treats the reference density as not available.